← Home All Mobile Robotics

AGV Voice Alarm Box SPK-5-24-485

Modbus RTU Not connected ไทย

Now playing

— stopped —
Sent 0 times Last
Melody Box model SPK-5-24-485 · RS485 · 12–36 V supply · 90 dB output · View product

Folder 0 is stop · 1255 map to folders AW001AW255 in the box
Load audio files yourself over the rear Micro USB port. WAV and MP3 supported

Volume

20
🔴 The device address is fixed at 1 and users cannot change it A different value must be requested when ordering
This means You cannot put two of these on one RS485 bus Duplicate addresses answer simultaneously and neither reply is readable
For several locations — request a different address when ordering · run separate cables · or add external speakers to one unit
0–28 (29 steps) — move the slider, then play again to apply
The box also has a volume knob on the back The two multiply With the knob turned down, commanding 28 is still quiet

Quick play

Press to play that folder immediately at the set volume — useful for finding which sound is in which folder

Communication log

This page uses Modbus RTU Every frame ends with CRC16 — this is what we stock

One play takes two frames: send volume first, then the play command. They are separate registers and cannot be written in one frame
Here you can read what the box actually holds with function 03. Use the "Read current values" button

🔴 The address is fixed at 1 and users cannot change it The manual states users can not modify, and there is no register for the address. A different value must be requested when ordering
Other: Vendor protocol · Choose model and control method